CVE-2018-5459
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X.
Published 8 y ago · modified 4 mo ago · JSON
Summary
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.
Exploit prediction (EPSS)
2.68% probability of exploitation in the next 30 days, higher than 86% of all scored CVEs.
CVSS scores
| Assigned by | Version | Score | Vector |
|---|---|---|---|
| NVD | 3.0 | 9.8 | CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H |
| NVD | 2.0 | 7.5 | AV:N/AC:L/Au:N/C:P/I:P/A:P |
Affected products
- n/a WAGO PFC200 Series
Classification
- Weakness
- CWE-287 Improper Authentication
References
- ics-cert.us-cert.gov /advisories/ICSA-18-044-01 · x_refsource_MISC, x_transferred
Sources
- CVE List: CVE-2018-5459
- NVD: CVE-2018-5459
vulnwire keeps one entry per vulnerability: the CVE id wins, then GHSA; records that alias each other are merged. Machine-readable: JSON.