5.3med

CVE-2017-9947

A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5.

Published 9 y ago · modified 4 mo ago · JSON

CVSS
5.3
v3.1 · CNA
CISA KEV
No
not known exploited
EPSS
8.2%
percentile 95%
Public exploits
0
none known

Summary

A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. A directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices.

CISA SSVC assessment

Exploitation
Proof of concept public
Automatable
yes
Technical impact
partial
Assessed
5 mo ago

Exploit prediction (EPSS)

8.19% probability of exploitation in the next 30 days, higher than 95% of all scored CVEs.

CVSS scores

Assigned byVersionScoreVector
CISA ADP3.15.3CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
NVD3.15.3CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
CNA3.15.3CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N
NVD2.05.0AV:N/AC:L/Au:N/C:P/I:N/A:N

Affected products

  • n/a APOGEE PXC and TALON TC BACnet Automation Controllers All versions <V3.5

Classification

Weakness
  • CWE-538 Insertion of Sensitive Information into Externally-Accessible File or Directory
  • CWE-22 Improper Limitation of a Pathname to a Restricted Directory

References

Sources

vulnwire keeps one entry per vulnerability: the CVE id wins, then GHSA; records that alias each other are merged. Machine-readable: JSON.