CVE-2017-6030
Schneider Electric Modicon PLCs Predictable Value Range from Previous Values
Published 9 y ago · modified 4 mo ago · JSON
Summary
A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.
CISA SSVC assessment
- Exploitation
- none
- Automatable
- yes
- Technical impact
- partial
- Assessed
- 5 mo ago
Exploit prediction (EPSS)
2.18% probability of exploitation in the next 30 days, higher than 82% of all scored CVEs.
CVSS scores
| Assigned by | Version | Score | Vector |
|---|---|---|---|
| CISA ADP | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L |
| NVD | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L |
| CNA | 3.1 | 6.5 | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L |
| NVD | 2.0 | 6.4 | AV:N/AC:L/Au:N/C:N/I:P/A:P |
Affected products
- Schneider Electric Modicon M221
- Schneider Electric Modicon M241
- Schneider Electric Modicon M251
Classification
References
- ics-cert.us-cert.gov /advisories/ICSA-17-089-02 · x_refsource_MISC, x_transferred
- securityfocus.com /bid/97254 · vdb-entry, x_refsource_BID, x_transferred
- github.com /cisagov/CSAF/blob/develop/csaf_files/OT/white/2017/icsa-17-089-02.json
Sources
- CVE List: CVE-2017-6030
- NVD: CVE-2017-6030
vulnwire keeps one entry per vulnerability: the CVE id wins, then GHSA; records that alias each other are merged. Machine-readable: JSON.