A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouc…

Published 9 y ago · modified 4 mo ago · JSON

CVSS
9.8
v3.0 · NVD
CISA KEV
No
not known exploited
EPSS
5.1%
percentile 92%
Public exploits
0
none known

Summary

A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.

Exploit prediction (EPSS)

5.05% probability of exploitation in the next 30 days, higher than 92% of all scored CVEs.

CVSS scores

Assigned byVersionScoreVector
NVD3.09.8CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
NVD2.010.0AV:N/AC:L/Au:N/C:C/I:C/A:C

Affected products

  • n/a Schneider Electric InduSoft Web Studio, InTouch Machine Edition

Classification

Weakness
  • CWE-306 Missing Authentication for Critical Functionality